Introduction
Filtration efficiency is an important factor when purchasing and selecting air filters. ASHRAE 52.2-2025 and ISO 16890 are two widely used standards for testing and evaluating general ventilation air filters. They use the MERV and ePM rating systems, respectively, to classify filter performance.
Both standards evaluate an air filter’s ability to remove airborne particles. However, they differ in test methods, particle size ranges, and efficiency evaluation methods. Understanding these differences helps buyers interpret product specifications correctly and avoid relying on filter ratings alone when selecting products for specific applications.
1. ASHRAE 52.2: evaluating filtration efficiency with MERV
ASHRAE 52.2 is a standard developed by the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). It evaluates the particle removal efficiency of general ventilation air-cleaning devices across different particle size ranges.
The standard uses particle counting and divides the test particles into three size ranges:
- E1: 0.3–1.0 μm
- E2: 1.0–3.0 μm
- E3: 3.0–10.0 μm
The test measures the filter’s particle removal efficiency in each size range. The results are then processed according to the standard’s prescribed procedures to determine the filter’s MERV rating.
MERV stands for Minimum Efficiency Reporting Value. The rating scale ranges from MERV 1 to MERV 16. In general, a higher MERV rating indicates better filtration efficiency for particles within the relevant size ranges.
It is important to understand that MERV does not represent the filtration efficiency for a single particle size. Instead, the rating reflects the filter’s performance across multiple particle size ranges. A particular MERV rating therefore does not mean that the filter achieves the same efficiency for all particles.
For buyers, MERV provides a useful way to compare filter performance. However, actual filter selection should also take into account airflow, initial pressure drop, and operating conditions.
2. ISO 16890: evaluating particle filtration performance with ePM
ISO 16890 is a standard developed by the International Organization for Standardization (ISO) for general ventilation air filters. Unlike the MERV rating system in ASHRAE 52.2, ISO 16890 uses the ePM classification system to evaluate filter efficiency across different particle size ranges.
Its main filter classifications include:
- ISO Coarse
- ISO ePM10
- ISO ePM2.5
- ISO ePM1
The ePM categories refer to filtration efficiency based on the mass of particulate matter within specific particle size ranges. A smaller number indicates that the category focuses on finer particles.
ISO 16890 evaluates a filter’s fractional efficiency across different particle sizes. It then combines these results with a standardized particle size distribution to calculate the corresponding ePM efficiency.
For example, an ePM1 60% rating means that the filter achieves an average ePM1 efficiency of 60%, calculated according to ISO 16890. It does not mean that the filter removes exactly 60% of all particles measuring 1 μm.
The ISO 16890 evaluation process also considers factors such as initial resistance and changes in filtration performance before and after conditioning. As a result, the ePM rating provides buyers with useful information about a filter’s particle removal performance. However, buyers should still consider other product specifications before making a selection.
3. ASHRAE 52.2 vs. ISO 16890: key differences and practical selection factors
Although both ASHRAE 52.2 and ISO 16890 evaluate the particle removal performance of general ventilation air filters, they use different test methods and classification systems. MERV and ePM ratings cannot be directly converted into one another.
The table below highlights their main differences:
| Comparison | ASHRAE 52.2 | ISO 16890 |
| Standard system | ASHRAE standard in the United States | International ISO standard |
| Filtration rating | MERV | ISO Coarse, ePM10, ePM2.5, ePM1 |
| Particle size ranges | Three ranges: E1, E2, and E3 | Evaluates particles across different size ranges |
| Evaluation method | Determines the MERV rating based on particle-counting efficiency across different size ranges | Combines fractional efficiency results with a standardized particle size distribution to calculate mass-based efficiency (ePM) |
| Main application | Evaluates the particle removal performance of general ventilation air filters | Evaluates the filtration performance of general ventilation air filters across different particle size ranges |
From a purchasing perspective, both standards help buyers understand an air filter’s particle removal performance. However, the filtration rating is only one factor in the selection process.
(1) Match filtration efficiency to actual requirements
Different applications require different levels of particle filtration. Before selecting a filter, buyers should identify the types of particles they need to control and the required filtration performance. They can then use the MERV or ePM rating to assess whether a product meets those requirements.
A higher rating does not necessarily mean a filter is the best choice for every application.
(2) Consider initial pressure drop and energy consumption
Air filters create resistance as air passes through them. Under the same airflow and test conditions, a higher initial pressure drop generally means the fan needs to work harder to overcome the resistance. This can increase energy consumption.
Buyers should therefore balance filtration efficiency with airflow resistance when selecting an air filter.
(3) Consider dust-holding capacity and replacement intervals
Dust-holding capacity indicates how much dust a filter can retain under specified test conditions. It is an important factor in evaluating filter performance over time.
For ventilation systems that operate continuously, buyers should consider both filtration efficiency and dust-holding capacity. These factors help estimate maintenance requirements, replacement intervals, and overall operating costs.
(4) Check installation requirements and operating conditions
An air filter’s dimensions, structural design, rated airflow, and operating environment all affect its suitability for a specific application.
Even filters with similar efficiency ratings may perform differently because of variations in filter media, construction, and design. Buyers should therefore check the available installation space, required airflow, ambient temperature, humidity, and other operating conditions before making a decision.
In summary, ASHRAE 52.2 and ISO 16890 provide standardized methods for evaluating air filter performance. However, a filter rating alone cannot provide a complete picture of product performance. Buyers should consider filtration efficiency, initial pressure drop, dust-holding capacity, and actual operating conditions together to make a more informed selection.
4. LANSIR’s testing capabilities and quality management
For air filter manufacturers, product performance must meet application requirements and undergo appropriate testing. In addition to MERV and ePM ratings, buyers should also consider a manufacturer’s testing equipment, laboratory capabilities, and quality management systems when evaluating potential suppliers.
(1) Filtration performance testing and laboratory capabilities
LANSIR has equipped its facilities with a range of testing equipment for air filter performance evaluation. This includes filter media performance test duct systems, comprehensive filter media testing platforms, environmental test chambers of different sizes, and gas adsorption efficiency and penetration test benches.
Its testing projects cover fractional filtration efficiency, pressure drop and airflow resistance, dust-holding capacity, and tests involving gases such as toluene, butane, nitrogen oxides, and sulfides. The company also conducts Clean Air Delivery Rate (CADR) testing.
Among these test items, fractional filtration efficiency, pressure drop, and dust-holding capacity are key indicators of air filter performance. They reflect a product’s particle removal capability, airflow resistance, and dust retention capacity, respectively.
To support its testing activities, LANSIR has obtained CNAS laboratory accreditation and inspection and testing institution qualification. These credentials relate to laboratory technical competence and the proper conduct of inspection and testing activities. The specific testing items and authorized scopes are subject to the relevant accreditation and qualification documents.
(2) Quality management and third-party testing
Beyond laboratory testing, a quality management system provides an important foundation for production and quality control. LANSIR has obtained ISO 9001 quality management system certification, as well as ISO 14001 environmental management system certification and ISO 45001 occupational health and safety management system certification. These systems support the company’s ongoing efforts to improve its management practices.
In addition, some LANSIR products have undergone testing by third-party organizations such as SGS and TÜV. These tests provide independent testing results for the relevant products. For projects with specific standards or performance requirements, buyers can review the test reports for the relevant product models to confirm the test items, results, and applicable standards.
With experience in the development and manufacturing of air filters and air purification equipment, LANSIR provides filtration products for a range of applications. For projects with specific requirements for filtration efficiency, operating airflow, or installation dimensions, customers can share their application conditions and product specifications with the company to discuss suitable products and customization options.